Smart PRO X

Filling

2 Pumps

Quick Guide

Start Float - Min Float

Plant

Smart Pro X - Riempimento - 1 pompa con galleggiante - Sonde di minima.webp

1

Elentek Panel

2

Submersible Pumps

3

Minimum Float

4

Alternation Float

5

Emergency Float Switch

6

Counterweight

Scheme

schema Smart Pro X - Riempimento - 1 pompa con galleggiante - Sonde di minima.webp

3

Minimum Float

4

Alternation Float

5

Emergency Float Switch

8

Alarm Systems (optional)

CMAX

Screenshot 2025-08-05 alle 10.56.08.png

Short-circuit C/MAX 

sfondo quadroni sezioni.webp

Dip Switch

Configuration

For this specific configuration, dip switches 5 and 8 must be set to ON.

WARNING: the modification of the dip switches must be done with the panel turned off

sfondo quadroni sezioni.webp

Legend

sfondo quadroni sezioni.webp

Legend

1

Allows you to enable the level alarm signal from the probe input or minimum level float (C-MIN-MAX input).


- In the OFF position, a change in input status does not trigger an alarm signal.

- In the ON position, a change in input status, depending on the emptying or filling function, triggers an alarm signal on the panel and activates the dry contact alarm output and the voltage alarm output.

2

Permette di selezionare il tempo di ritardo di attivazione dell’intervento termico di 5 secondi o 10 secondi.

L’impostazione di questo parametro permette di evitare l’intervento dello scatto termico per sovracorrente durante l’avvio del motore, evitando in questo modo la corrente di spunto.


- In posizione OFF il ritardo di intervento amperometrico all’avvio del motore è di 5 secondi.

- In posizione ON il ritardo di intervento amperometrico all’avvio del motore è di 10 secondi.

3

Allows you to enable the clicson input for motor overtemperature monitoring.


- In the OFF position, the clicson inputs are activated.

- In the ON position, the clicson inputs are deactivated.

If the inputs are deactivated and the motors do not have a thermal cutout, it is not necessary to

jump them.

4

Permette di selezionare se l’allarme di sovratemperatura motore dato dagli

ingressi clicson T1 e T2 deve essere ripristinato manualmente, tenendo premuto il pulsante AUT, o in automatico.


- In posizione OFF in caso di sovratemperatura motore il ripristino è manuale.

- In posizione ON il ritardo di intervento termico motore sarà di 10 secondi.

5

Allows you to select whether the C-MIN-MAX probe input is used in emptying or filling mode.


- In the OFF position (filling), the input will be used to enable the system in the absence of water. The C-MIN-MAX input must be open to enable the system. If using an on/off float control, use the C-MAX input.

- In the ON position (emptying or pressurizing), the input will be used to enable the system in the presence of water. The C-MIN-MAX input must be closed to enable the system. If using an on/off float control, use the C-MAX input.


NB: If you are not using a minimum level control, jumper the C-MAX input.

6

Allows you to activate the self-holding function for the

start/stop floats for wastewater drainage.

With this setting, you must connect the stop float to the C-MAX input and the start floats to G/P1 and G/P2.


- In the OFF position, the self-holding function of the floats is deactivated.

- In the ON position, the self-holding function of the floats is activated.


NB: Do not activate on pressurization systems. Activate during draining only if the C-MIN-MAX input is used with a float or level probes.

7

Allows you to activate a delay before the board is enabled in the event of a power failure.


- In the OFF position, the panel will activate immediately upon restoration of the power supply.

- In the ON position, upon restoration of the power supply, the panel will activate after 30 seconds.


Note: After a power failure, the panel will reactivate while maintaining the previously set AUT-0-MAN status.

8

Allows you to enable the automatic motor switching function.


- In the OFF position, input G/P1 directly and independently controls output motor 1, and input G/P2 directly and independently controls output motor 2.

- In the ON position, each call from input G/P1 activates the motor outputs alternately, and if input G/P2 is also activated, both motors will operate.

The enabled switcher allows, in addition to alternating the motors with each call from input G/P1, switching in the event of:

• Overcurrent of one motor.

• Standby of one motor.

• Lack of water upon subsequent automatic reset.

Diagnostics

If the system does not start, evaluate the CONDUCTIVITY status of the liquid and the position of the SENSITIVITY TRIMMER (SENS. PROBE).

Trimmer Probe Sensitivity

SENS PROBE.webp

Set the sensitivity based on the conductive characteristics of the liquid.

HIGHLY CONDUCTIVE Liquid: set LOW value (tending to 1)

POORLY CONDUCTIVE Liquid: set HIGH value (tending to 9)

Note: factory setting is set to MEDIUM

Current Motor Trimmer

TRIMMER MOTORI.webp

Adjust with appropriate equipment (or small screwdriver) the MIN current TRIMMER and MAX current TRIMMER associated with Pump M1 and Pump M2.

sfondo tondi sezioni.webp

MINIMUM CURRENT TRIMMER

Adjust with -10% - 15% compared to the nominal motor current*

sfondo tondi sezioni.webp

MAXIMUM CURRENT TRIMMER

Adjust with a +10% + 15% compared to the nominal motor current*

* Data available on the nameplate of the electric pump or, if illegible, use a clamp meter, ensuring that the pump is operating under normal conditions. If there are further reading difficulties, proceed to assisted calibration.

Assisted Calibration

Assisted Calibration

MINIMUM current assisted calibration

Access the parameter setup and select the parameter: "CURRENT SETTING M1-M2".

The display shows the threshold value corresponding to the MIN/MAX current trimmers adjustment.

From this screen, you can start the motor manually and the current draw is displayed.

Adjust the M1/M2 MIN trimmer to a value approximately 15% lower

than the current draw.

Note: To calibrate the minimum current, the motor must be started in the presence of water.

The current scale is related to the power of the control panel model: from 1 to 17 Amps (7.5 kW) or from 15 to 31 Amps (15 kW).

Assisted calibration MAXIMUM current

Access the parameter setup and select the parameter: "CURRENT SETTING M1-M2".

The display shows the threshold value corresponding to the MIN/MAX current trimmers adjustment.

From this screen, you can start the engine manually and the absorbed current value is shown on the display; then adjust the M1/M2 MAX trimmer to a value approximately 15% higher than the absorbed value.

Note: To calibrate the maximum current, the motor must be started in the presence of water.

The current scale is related to the power of the control panel model: from 2 to 18 Amps (7.5 kW) or from 16 to 32 Amps (15 kW).

sfondo quadroni sezioni.webp

Display

Max and Min Current M1 - M2

DISPLAY GENERICO.webp
  1. With the screen on, on the page shown, press and hold SETUP for 5 seconds to enter the SETTINGS menu.
  2. Press SETUP again to scroll through the menu.
  3. SETTINGS:
  • Maximum Current M1 and M2 (adjusts based on motor current)
  • Minimum Current M1 and M2 (adjusts based on motor current)For further controls and protections, refer to the SETTINGS MENU section of the manual.

For further controls and protections, refer to the SETTINGS MENU section of the manual.

sfondo quadroni sezioni.webp

Additional Display Functions

sfondo quadroni sezioni.webp

Display - Additional functions

Dip Switch Display

WARNING: the modification of the dip switches must be done with the panel turned off

DIP SWITCH DISPLAY.webp

Basic configuration

By default, the DIP SWITCH of the display, to activate additional functions, is set to OFF

Dip Switch Display - Additional functions

Dip Switch Display - Additional functions

1

DIP-SWITCH 1 - Inverting NO/NC inputs (G/P1 - G/P2 - G.A.)



OFF ⬇ Normally open alarm inputs.

ON ⬆ Normally closed inputs.


DIP-SWITCH 1 allows you to invert the enabling of the digital inputs G/P1 - G/P2 - G.A.


In the OFF position, the normally open inputs enable the system to close the contact.

In the ON position, the normally closed inputs enable the system to open the contact.

2

DIP-SWITCH 3 - Self-test enable



OFF ⬇ Motor self-test disabled

ON ⬆ Motor self-test enabled


DIP-SWITCH 3 enables the motor self-test.


In the OFF position, the self-test is disabled.

In the ON position, the self-test is enabled.


The self-test has a fixed, non-adjustable time and will enable the pump, or pumps, depending on the control panel model, for 2 seconds every 48 hours.

A pump self-test can only be activated if the control panel's Automatic function is enabled.

3

DIP-SWITCH 3 - Self-test enable



OFF ⬇ Motor self-test disabled

ON ⬆ Motor self-test enabled


DIP-SWITCH 3 enables the motor self-test.


In the OFF position, the self-test is disabled.

In the ON position, the self-test is enabled.


The self-test has a fixed, non-adjustable time and will enable the pump, or pumps, depending on the control panel model, for 2 seconds every 48 hours.

A pump self-test can only be activated if the control panel's Automatic function is enabled.

4

DIP-SWITCH 4 - Push-to-run or impulse manual button



OFF ⬇ Push-to-run manual button.

ON ⬆ Impulse manual button.


DIP-SWITCH 4 allows you to set the manual button's operation.


In the OFF position, the manual button enables the motor by holding the button down; releasing it stops the motor.

In the ON position, the manual button enables the motor, and the OFF button stops the motor; in this mode, the motor protections are active.

Ti è stata utile questa guida?

Lasciaci una recensione e iscriviti alla newsletter per rimanere sempre aggiornato sui nostri prodotti e funzionalità

PRIVACY E COMUNICAZIONI

Dichiaro di avere compiuto sedici anni, e se minore di sedici, di essere stato autorizzato dal titolare della responsabilità genitoriale, pertanto acconsento al trattamento dei miei dati personali così come indicato nella Privacy Policy.

Acconsento al trattamento dei miei dati personali. Per l’inoltro della newsletter, le comunicazioni via telefono (sms, WhatsApp, telefonata vocale). Informativa modulo contatti e richiesta informazioni.

Privacy policy

Cookies policy

Copyright 2023 © Elentek srl

VAT No. 04534630282

Share Capital paid up 110,000 €

REA: PD - 397546

bottom of page