Plant

1
Elentek Panel
2
Surface Pumps
3
Bell Float Switch
4
Non-return valves
5
Drainage
Scheme

3
Bell Float Switch
8
Alarm Systems (optional)
CMAX

Short-circuit C/MAX

Set Up
Configuration
To access the settings menu, press the SETUP button for 3 seconds. PUMP ROTATION ACTIVATION This parameter allows the pump exchange to be activated with each call from the floats or pressure switches; furthermore, if the main pump goes into thermal protection (overcurrent), the second pump is enabled (setting N disables the START/STOP function).
WARNING: the modification of the dip switches must be done with the panel turned off

Legend

Legend
Diagnostics
If the system does not start, evaluate the CONDUCTIVITY status of the liquid and the position of the SENSITIVITY TRIMMER (SENS. PROBE).
Trimmer Probe Sensitivity

Set the sensitivity based on the conductive characteristics of the liquid.
HIGHLY CONDUCTIVE Liquid: set LOW value (tending to 1)
POORLY CONDUCTIVE Liquid: set HIGH value (tending to 9)
Note: factory setting is set to MEDIUM
Current Motor Trimmer


MINIMUM CURRENT TRIMMER
Adjust with -10% - 15% compared to the nominal motor current*

MAXIMUM CURRENT TRIMMER
Adjust with a +10% + 15% compared to the nominal motor current*
* Data available on the nameplate of the electric pump or, if illegible, use a clamp meter, ensuring that the pump is operating under normal conditions. If there are further reading difficulties, proceed to assisted calibration.
Assisted Calibration
Assisted Calibration

Display
Max and Min Current M1 - M2

- With the screen on, on the page shown, press and hold SETUP for 5 seconds to enter the SETTINGS menu.
- Press SETUP again to scroll through the menu.
- SETTINGS:
- Maximum Current M1 and M2 (adjusts based on motor current)
- Minimum Current M1 and M2 (adjusts based on motor current)For further controls and protections, refer to the SETTINGS MENU section of the manual.
For further controls and protections, refer to the SETTINGS MENU section of the manual.

Additional Display Functions

Display - Additional functions
Dip Switch Display
WARNING: the modification of the dip switches must be done with the panel turned off

Basic configuration
By default, the DIP SWITCH of the display, to activate additional functions, is set to OFF
Dip Switch Display - Additional functions
Dip Switch Display - Additional functions
1
DIP-SWITCH 1 - Inverting NO/NC inputs (G/P1 - G/P2 - G.A.)
OFF ⬇ Normally open alarm inputs.
ON ⬆ Normally closed inputs.
DIP-SWITCH 1 allows you to invert the enabling of the digital inputs G/P1 - G/P2 - G.A.
In the OFF position, the normally open inputs enable the system to close the contact.
In the ON position, the normally closed inputs enable the system to open the contact.
2
DIP-SWITCH 3 - Self-test enable
OFF ⬇ Motor self-test disabled
ON ⬆ Motor self-test enabled
DIP-SWITCH 3 enables the motor self-test.
In the OFF position, the self-test is disabled.
In the ON position, the self-test is enabled.
The self-test has a fixed, non-adjustable time and will enable the pump, or pumps, depending on the control panel model, for 2 seconds every 48 hours.
A pump self-test can only be activated if the control panel's Automatic function is enabled.
3
DIP-SWITCH 3 - Self-test enable
OFF ⬇ Motor self-test disabled
ON ⬆ Motor self-test enabled
DIP-SWITCH 3 enables the motor self-test.
In the OFF position, the self-test is disabled.
In the ON position, the self-test is enabled.
The self-test has a fixed, non-adjustable time and will enable the pump, or pumps, depending on the control panel model, for 2 seconds every 48 hours.
A pump self-test can only be activated if the control panel's Automatic function is enabled.
4
DIP-SWITCH 4 - Push-to-run or impulse manual button
OFF ⬇ Push-to-run manual button.
ON ⬆ Impulse manual button.
DIP-SWITCH 4 allows you to set the manual button's operation.
In the OFF position, the manual button enables the motor by holding the button down; releasing it stops the motor.
In the ON position, the manual button enables the motor, and the OFF button stops the motor; in this mode, the motor protections are active.
Ti è stata utile questa guida?
Lasciaci una recensione e iscriviti alla newsletter per rimanere sempre aggiornato sui nostri prodotti e funzionalità